Home
>
Business Customers
>
Products & Services
>
System Solutions
Electrical / Environmental Specifications
|
| |
Maximum Peak Surge Current (all phases)
40KA |
Maximum Clamping Voltage Level @ 40KA (all phases)
1650VDC |
Start Clamping Voltage Level @ 1 ma (all phases)
430VDC
|
Accelerated Life Test
13KV, 1.2/50 usec. open circuit, 5.5KA, 8/20 usec. short circuit, 100 surge cycles, six seconds apart. No failure or arcing allowed. |
Surge arresters still in excellent condition at end of tests.No arcing. |
Temporary Overvoltage
Continuous, five minutes, maximum line voltage without thermal runaway. |
368VAC |
End of Life Failure Mode
While in overvoltage-induced thermal runaway, apply 7KA at operating voltage. Surge arrester must fail-safe without faulting the AC line. No arcing allowed. |
Surge Arrester fails safe-surge element punctures, safety fuse opens, LED turns off, no fire, slight puff of smoke out connector wire opening. AC line not faulted. No arcing. |
Enclosure Flammability
(550-degree C or greater) |
9600-degree C., UI. 94 VI |
Ultra-Violet Resistance
|
Good UV stability in tropical conditions |
Thermal Withstand
|
80-degree C |
Salt-Fog Corrosion Resistance
|
Very good |
Enclosure Dimensions
|
12 inches x 10 inches x 4 inches |
Recommended "Hole Size" for Mounting Connector
|
1.12 inches |
|
|
|
| |
 |
 |
Surge Protection